期刊
GEOTHERMICS
卷 40, 期 2, 页码 136-143出版社
PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.geothermics.2011.02.003
关键词
Borehole heat exchangers; Heat transfer; Finite line-source method; Ground-source heat pumps; Thermal response test
资金
- European Union Commission [GROUND-MED FP7-ENERGY-2007-2-TREN-218895, 043340, Geotrainet - IEE/07/581]
- Spanish Ministry of Education and Science [ENE2008-00599/CON]
- Government of Valencia [GV/2008/292, PAID-06-09/2734]
This paper presents a method of subtracting the effect of atmospheric conditions from thermal response test (TRT) estimates by using data on the ambient air temperature. The method assesses effective ground thermal conductivity within 10% of the mean value from the test, depending on the time interval chosen for the analysis, whereas the estimated value can vary by a third if energy losses outside the borehole are neglected. Evaluating the same test data using the finite line-source (FLS) model gives lower values for the ground thermal conductivity than for the infinite line-source (ILS) model, whether or not heat dissipation to ambient air is assumed. (C) 2011 Elsevier Ltd. All rights reserved.