Capacity reduction and fire load factors corresponding to the load and resistance factor design (LRFD) format are developed for steel columns exposed to fire. A sample deterministic framework to determine fire and steel temperatures and the capacity of steel columns is adopted for this analysis to structure the methodology. A specific number of parameters that affect the structural response, including the fire load, ratio of floor area to the total area of the fire compartment, opening factor, thermal absorptivity of compartment boundaries, thickness, density and thermal conductivity of insulation, dead load, and live load are taken as random variables. Mechanical and sectional properties of steel (e.g., yield strength, cross-sectional area, etc.), are also considered to be random variables. The effect of active fire protection systems (e.g., sprinklers, smoke and heat detectors, fire brigade, etc.), in reducing the probability of occurrence of a severe fire is included. Given the choice of framework and based on detailed reliability analyses, it is shown that the capacity reduction and fire load factors should vary depending on the presence of active fire protection systems in a building. (C) 2011 Elsevier Ltd. All rights reserved.