期刊
EXPERIMENTAL THERMAL AND FLUID SCIENCE
卷 46, 期 -, 页码 183-190出版社
ELSEVIER SCIENCE INC
DOI: 10.1016/j.expthermflusci.2012.12.010
关键词
-
资金
- Catedra Fundacion Antonio Aranzabal - University of Navarra
Experimental measurements in a spray cooling test rig were carried out for two different heater surface roughnesses and for two different types of nozzles with the dielectric refrigerant R134a. In this paper, results of the heat transfer measurements are presented. The analysis of the results explains the influence of the volumetric flow rate, the surface roughness and the type of nozzle (through the spray parameters) on the spray cooling boiling curve, on the Nusselt number and on the efficiency. It has been found that the effect of a smooth roughness is to delay the onset of the nucleate boiling, but once this regime has started, boiling is so fast that the CHF (Critical Heat Flux) is reached at lower heater temperatures and lower heat fluxes. In a companion paper the sprayed refrigerant film thickness measurements and its relation with the heat transfer measurements are presented. (C) 2012 Elsevier Inc. All rights reserved.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐