3.9 Article

Numerical calculation of the corona onset voltage for bundle conductors for HVDC transmission line

期刊

出版社

WILEY
DOI: 10.1002/etep.406

关键词

charge simulation method; onset corona voltage and electric field; transmission line; bundle conductors

资金

  1. China Electrical Power Research Institute

向作者/读者索取更多资源

The corona onset voltage (COV) for bare overhead bundle conductors for transmission lines has been investigated using numerical calculations and the gas discharge theory. First, an accurate numerical method, the charge simulation method, was used to calculate the electric field distribution in the vicinity of bare sub-conductors in bundles. Then the electric field values and a criterion from the gas discharge theory were used to evaluate the onset voltage for negative coronas on the bare sub-conductors. The COVs obtained are in good agreement with literature data for laboratory models and full-scale test lines. Some numerical results for the COV for six-bundle conductors are also discussed. Copyright (C) 2010 John Wiley & Sons, Ltd.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

3.9
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据