4.7 Article

Experimental study on the thermal performance of mechanical cooling tower with rotational splash type packing

期刊

ENERGY CONVERSION AND MANAGEMENT
卷 87, 期 -, 页码 530-538

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.enconman.2014.07.036

关键词

Wet cooling tower; Counter flow; Rotational packing; Thermal performance

向作者/读者索取更多资源

This paper deals with an experimental investigation of thermal performance of a forced draft counter flow wet cooling tower filled with a rotational splash type packing. Tower's parameters are compared when the packing has been rotated and when it does not rotate (like common existing towers). However, no references regarding the effect of the rotational packing on the cooling tower performance have been found in the reviewed bibliography. The packing has 0.85 m(2) area and consists of six horizontal wooden slats fixed on a threaded metallic shaft. This investigation is carried out for three inlet air temperatures 27 degrees C, 34 degrees C and 41 degrees C while water temperature is kept constant at 45 degrees C. The ranges of packing velocities are between 0 to 17 RPM and also several ranges of water to air flow rate ratio are experimented: 0.4

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据