Grid connected PV system; Photovoltaic; Malaysia
资金
- Research Council of the Sultanate of Oman [ORG SU EI 11 010]
- Research Council of Oman
This paper presents a field operation experience for a grid connected PV system under tropical climate. The system is consisted of a 5 kWp photovoltaic (PV) array and a 6 kW DC/AC inverter. The operation performance data are recorded in order to develop accurate mathematical models for the system as well as to evaluate the productivity of the system. The experiment results show that, the average PV performance (the ratio of the theoretical performance to the actual performance) is 73.12% while the average inverter performance (the ratio of the theoretical inverter efficiency to the actual inverter efficiency) is 98.56%. Moreover, it is found that the daily yield factor of the PV system is 2.51 kW h/kWp day while, the capacity factor is 10.47%. However, it is concluded that the productivity of the system is below the prospected rate and thus, an inspection of the system must be done in order to diagnose the problem of the system's low productivity. This paper presents worthwhile information for those who are interested in PV system installation in Malaysia and nearby country. (C) 2013 Elsevier Ltd. All rights reserved.