期刊
ENERGY CONVERSION AND MANAGEMENT
卷 52, 期 7, 页码 2598-2603出版社
PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.enconman.2010.12.015
关键词
Evaporative cooling pads; Corrugated papers; Evaporative cooler
In the present work, thermal performance of two types of cellulosic pads (5090 and 7090) which were made from corrugated papers has been studied experimentally. Samples were tested in a sub sonic wind tunnel made from polyethylene. The pads areas are 0.5 x 0.5 m(2) with 75, 100 and 150 mm thicknesses. Pressure drop, humidity variation, evaporated water and effectiveness have been investigated for several inlet air velocities. The results show that overall pressure drop and amount of evaporated water increase by increasing the inlet air velocity and thickness in both types of pads. On the other hand, effectiveness and humidity variation decrease by increasing inlet air velocity. (C) 2010 Elsevier Ltd. All rights reserved.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐