4.7 Article

Investigating the performance of cellulosic evaporative cooling pads

期刊

ENERGY CONVERSION AND MANAGEMENT
卷 52, 期 7, 页码 2598-2603

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.enconman.2010.12.015

关键词

Evaporative cooling pads; Corrugated papers; Evaporative cooler

向作者/读者索取更多资源

In the present work, thermal performance of two types of cellulosic pads (5090 and 7090) which were made from corrugated papers has been studied experimentally. Samples were tested in a sub sonic wind tunnel made from polyethylene. The pads areas are 0.5 x 0.5 m(2) with 75, 100 and 150 mm thicknesses. Pressure drop, humidity variation, evaporated water and effectiveness have been investigated for several inlet air velocities. The results show that overall pressure drop and amount of evaporated water increase by increasing the inlet air velocity and thickness in both types of pads. On the other hand, effectiveness and humidity variation decrease by increasing inlet air velocity. (C) 2010 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据