4.7 Article

Experimental investigation of performance of vapor ejector refrigeration system using refrigerant R123

期刊

ENERGY CONVERSION AND MANAGEMENT
卷 49, 期 5, 页码 953-961

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.enconman.2007.10.006

关键词

refrigeration system; constant area ejector; R123; optimum; performance

向作者/读者索取更多资源

In the present study, a novel ejector was designed based oil a constant area ejector model and manufactured in order to investigate the performance of an ejector refrigeration system in a wider operating range. The ejector, with movable primary nozzle, was mounted oil the system that was previously constructed for low pressure refrigerants. The modified refrigeration system has been tested using hot water as driving fluid and R123 as working fluid. The effects of the operating temperatures oil the cooling capacity and performance coefficient of the system were investigated experimentally when the primary nozzle position was optimum at the ejector area ratio of 9.97. As a result, a performance coefficient of 0.39 was obtained at the vapor generator temperature 98 degrees C, the evaporator temperature 10 degrees C and critical condenser pressure 129 kPa. (C) 2007 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据