期刊
ENERGY AND BUILDINGS
卷 57, 期 -, 页码 132-143出版社
ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2012.10.048
关键词
Air handling unit; Sensor; Fault detection; Fractal correlation dimension; Statistical residual
资金
- National Natural Science Foundation of China [50976066, 51006066]
For the air handling unit (AHU) sensor fault detection, the classical fault detection methods based on statistical residual evaluation are difficult to detect small bias fault especially under noisy conditions. On the other hand, a novel technique using fractal correlation dimension (FCD) algorithm can identify a tiny variation of curve fractal characteristic but needs a period of time. To balance their strengths as well as weaknesses, a hybrid model-based fault detection technique is developed by combining these two methods. The simulated data obtained from the TRNSYS simulation platform are used to validate the hybrid fault detection strategy. And a prediction model using support vector regression (SVR) is developed to obtain the fault-free references. Under a noise ranging from -0.3 degrees C to +0.3 degrees C, the technique is validated to detect six fixed biases of the supply air temperature sensor under three different load conditions. Given a specified threshold, the hybrid technique can identify the large bias faults such as +/- 0.5 degrees C by statistical residuals and can detect small faults of +/- 0.2 degrees C by FCD deviations. For the dynamic and nonlinear systems, FCD-based approach is more suitable for fault detection than for fault diagnosis. Crown Copyright (c) 2012 Published by Elsevier B.V. All rights reserved.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐
暂无数据