4.7 Article

Exergy analysis of borehole thermal energy storage system for building cooling applications

期刊

ENERGY AND BUILDINGS
卷 49, 期 -, 页码 568-574

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2012.03.013

关键词

Borehole thermal energy storage; Building; Exergy; Efficiency; Ground source heat pumps

资金

  1. TUBITAK, Scientific and Technological Research Council of Turkey
  2. University of Ontario Institute of Technology

向作者/读者索取更多资源

In this study, exergy analysis of a borehole thermal energy storage system (BTES) for cooling season is carried out. A comprehensive case study is conducted based on the system at University of Ontario Institute of Technology in Oshawa, Canada, and actual thermal load data are employed for analysis. The exergy destruction rates of each system component and overall system are calculated and studied for comparison purposes. It is determined from the analysis that the exergy destructions in a system particularly take place in condensers of cooling systems. Also, it is found that condenser and evaporator temperatures have strong effects on the exergetic performance of the system. For system performance analysis and improvement, exergy efficiencies of the overall BTES are investigated and determined to be a maximum of 62%. (C) 2012 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据