A model for integrating passive and low energy airflow components into low rise buildings

期刊

ENERGY AND BUILDINGS
卷 49, 期 -, 页码 148-157

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2012.02.002

关键词

Integrated multi-zone ventilation model; Solar chimney; Wind-induced earth-air tunnel; Natural ventilation; Passive cooling

向作者/读者索取更多资源

Integrating passive systems such as cross and stack ventilation, a solar chimney, a wind tower or an earth-air tunnel into a building envelope has the potential to significantly reduce the ventilation and air-conditioning demand on buildings. However the application of combination of these features in low rise contemporary buildings is limited. Among the major reasons, is the lack of simple building modelling techniques preventing effective integrated passive systems. Existing coupled multi-zone airflow and thermal modelling software such as COMIS-TRNSYS, CONTAM-TRNSYS or TRNFLOW do not include the passive airflow components which require simultaneous prediction of temperature and airflow rate in the components such as solar chimneys and wind-induced earth-air tunnels. This paper develops an integrated model incorporating these passive airflow components into a coupled multi-zone ventilation and building thermal model. The model is validated against COMIS-TRNSYS software for a lightweight building with large openings. The prediction of each passive airflow component is validated with available published analytical and experimental findings. The solar chimney model is able to predict reverse flow and accurately predicts the air temperature in the chimney. The earth air tunnel (EAT) considers the transient heating up effect of the soil during operation and predicts the outlet air temperature. (C) 2012 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据