4.7 Article

Calculation of transient heat transfer through the envelope of an underground cavern using Z-transfer coefficient method

期刊

ENERGY AND BUILDINGS
卷 48, 期 -, 页码 190-198

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2012.01.040

关键词

Underground caverns; Unstable heat transfer; Z-transfer function

资金

  1. National Nature Science Foundation of China [51178482]

向作者/读者索取更多资源

A Z-transfer function method is proposed to calculate transient heat flow through the envelope of an underground cavern in this paper. The envelope of an underground cavern has great heat capacity and high thermal inertia. In order to obtain the correct Z-transfer coefficients, indoor air temperature is expressed as a superposition of mean annual temperature, annual temperature wave and daily temperature wave. Corresponding to the three types of temperatures, three heat flows are calculated separately, and then are superposed. The thermal zones formed by annual temperature wave and daily temperature wave are different; thus, the ratio of amplitude frequency characteristics of the transfer functions is proposed to define the boundaries of the two different thermal systems. After transforming an underground cavern into an equivalent cylinder, the Z-transfer function coefficients of two thermal systems are calculated. Case study shows that heat fluxes at interior surface calculated by Z-transfer coefficient method have good agreement with those by numerical finite difference method, and the deviation between the results from two methods is only 1% of that from numerical method. However, the computation time of Z-transfer coefficient method is less than 1% of that of numerical method. (C) 2012 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据