4.7 Article

Reduced-scale model study of ventilation for large space of generatrix floor in HOHHOT underground hydropower station

期刊

ENERGY AND BUILDINGS
卷 43, 期 4, 页码 1003-1010

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2010.12.026

关键词

Mechanical ventilation; Hydropower station; Air distribution; Non-uniform coefficient; Energy efficiency coefficient

资金

  1. National Science Foundation of China [50778145, 50878177]

向作者/读者索取更多资源

A research project was undertaken on 1:20 reduced-scale model to investigate the air distribution effectiveness in two supply air modes in the generatrix floor in HOHHOT pumped-storage underground hydropower station. A series of tests (including temperature and air velocity) for 6 cases were performed in 48 various operating conditions. The air distribution was evaluated on the basis of non-uniform coefficient and energy efficiency coefficient principle by calculating dimensionless temperature and the dimensionless velocity. The results showed that mechanical air supply was superior to vertical pressure-gradient air supply. In the mode of mechanical air supply, the best supply air rate and case were determined. Moreover, changing heat sources (50%Q, 75%Q, 100%Q and 125%Q) had little effect on the air distribution in the best supply air case, which verified ventilation effectiveness and reliability. The experimental findings were useful for optimizing the ventilation design in a large space with complex heat sources. (C) 2010 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据