CO2-based demand controlled ventilation under new ASHRAE Standard 62.1-2010: a case study for a gymnasium of an elementary school at West Lafayette, Indiana

期刊

ENERGY AND BUILDINGS
卷 43, 期 11, 页码 3216-3225

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2011.08.021

关键词

ASHRAE 62.1; Demand controlled ventilation; Energy consumption; Indoor air quality; Control strategy; Schools

资金

  1. Division Of Computer and Network Systems
  2. Direct For Computer & Info Scie & Enginr [0751101] Funding Source: National Science Foundation

向作者/读者索取更多资源

CO2-based demand controlled ventilation had been tried and tested in the United States under the old ASHRAE Standard 62 Ventilation for Acceptable Indoor Air Quality, but this had since been replaced by ASHRAE Standard 62.1 and little is known on the field about the relative performances of CO2-based demand controlled ventilation between the old and new ventilation standards. In view of that, this paper presents a case study for an American elementary school gymnasium in order to compare the implementation of CO2-DCV under the old and new ventilation standards in terms of control strategies involved, the resulting energy savings, and indoor air quality associated with each strategy. The results indicate that, compared to the existing fixed ventilation rate strategy at which the ventilation rate is always 5% of the total supply air flow, a cooling coil energy savings of 0.03% and 1.86% can be achieved using an occupancy detection control strategy under the new ASHRAE 62.1 and old ASHRAE 62 respectively, while preserving thermal comfort and indoor air quality. (C) 2011 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据