4.7 Article

Experience on the application of a ground source heat pump system in an archives building

期刊

ENERGY AND BUILDINGS
卷 43, 期 11, 页码 3263-3270

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2011.08.029

关键词

Ground source heat pump system; Archives building; Energy conservation

资金

  1. Special Fund of Higher Education Doctorate Subject [200802481115]
  2. Shanghai Commission of Science and Technology [09160700200]

向作者/读者索取更多资源

A ground source heat pump (GSHP) system was designed and constructed in Minhang archives of Shanghai. As a demonstration project, it is the first archives to use a GSHP system in China. The system consists of two heat pumps with the rated cooling capacity of 500 kW for each and 280 boreholes with 80 m in depth. In the cooling mode, the heat extraction from the condenser of the heat pump was divided: part of it was rejected to the soil while the rest was used to reheat the air in air handling units. The GSHP system has continuously run for nearly two years. It was shown that the indoor thermal environment met the Archives Design Code issued by China national archives. Compared with an air source heat pump system which is widely used in archives buildings, the operating cost of the GSHP system is reduced by 55.8% and the payback time is about two years. Owing to its great potential in energy conservation, such kind of GSHP system is testified to be applicable to the air-conditioning systems of the archives buildings. Besides, the applications of GSHP systems corresponding to different climatic zones of China were analyzed. (C) 2011 Elsevier By. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据