Performance analysis of liquid desiccant based air-conditioning system under variable fresh air ratios

期刊

ENERGY AND BUILDINGS
卷 42, 期 12, 页码 2457-2464

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2010.08.027

关键词

Liquid desiccant; Air-conditioning; Performance analysis; Fresh air ventilation

资金

  1. Internal Competitive Research Grant (ICRG) of the Hong Kong Polytechnic University [G-YG49]
  2. Environment and Conservation Fund (ECF) of Hong Kong

向作者/读者索取更多资源

In conventional air-conditioning system, fresh air volume is always restricted to save energy, which sacrifices indoor air quality (IAQ) to some extent. However, removing the latent load of air by liquid desiccant rather than by cooling is an alternative way of reducing energy consumption. Therefore, IAQ can be improved by increasing the volume of fresh air introduced into an air-conditioning system. In this paper, a liquid desiccant based air-conditioning system is studied, with the system performance under various fresh air ratios analyzed using simulation tests. In addition, the proposed system and a conventional system are compared. In the proposed system, with the increase in fresh air ratio, the heating load for solution regeneration rises, the dehumidification efficiency increases and the regeneration efficiency drops. The coefficient of performance (COP) of the liquid desiccant based system decreases sharply when the fresh air ratio exceeds 60%. The results also show that the proposed system can save power notably. The maximum power saving ratio is 58.9% when the fresh air ratio is 20%; however, the ratio drops when the fresh air ratio increases. These findings will be beneficial in the selection of fresh air ventilation strategies for liquid desiccant based air-conditioning systems. (C) 2010 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据