4.7 Article

A criterion for the assessment of the reliability of ASHRAE conduction transfer function coefficients

期刊

ENERGY AND BUILDINGS
卷 42, 期 9, 页码 1426-1436

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2010.03.012

关键词

CTF coefficients; ASHRAE heat balance method; Thermal building simulation

向作者/读者索取更多资源

This paper presents a new mathematical approach, which, when applied to conduction transfer functions (CTFs) of a multi-layered wall, is able to predict the reliability of building simulations. This new procedure can be used to identify the best set of CTF coefficients, which are a critical point at the core of the ASHRAE calculation methodology founded on the transfer function method. To evaluate the performance of different CTF coefficient sets, the authors performed a large number of thermal simulations on the multi-layered walls included in the ASHRAE Handbook, volume fundamentals, and on other walls typical of Mediterranean building heritage. Those data were employed to test an algorithm able to assess the reliability of the simulations. The numerical results show that it is possible to select the optimal number of coefficients on the basis of the size of the poles of a CTF. The proposed criterion, which employs a pole threshold value, is highly accurate, fast and easy to integrate in the most diffuse building simulation tools. (C) 2010 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据