4.7 Article

Comparison between design and actual energy performance of a HVAC-ground coupled heat pump system in cooling and heating operation

期刊

ENERGY AND BUILDINGS
卷 42, 期 9, 页码 1394-1401

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2010.03.008

关键词

Heating and cooling systems; Ground coupled heat pump; Energy efficiency; Computer simulation; Experiments

资金

  1. Spanish Government [ENE2008-00599/CON]
  2. European Commission [IEE/07/581/S12.499061]

向作者/读者索取更多资源

This work compares the experimental results obtained for the energy performance study of a ground coupled heat pump system with the design values predicted by means of standard methodology. The system energy performance of a monitored ground coupled heat pump system is calculated using the instantaneous measurements of temperature, flow and power consumption and these values are compared with the numerical predictions. These predictions are performed with the TRNSYS software tool following standard procedures taking the experimental thermal loads as input values. The main result of this work is that simulation results solely based on nominal heat pump capacities and performances overestimate the measured overall energy performance by a percentage between 15% and 20%. A sensitivity analysis of the simulation results to changes in percentage of its input parameters showed that the heat pump nominal coefficient of performance is the parameter that mostly affects the energy performance predictions. This analysis supports the idea that the discrepancies between experimental results and simulation outputs for this ground coupled system are mainly due to heat pump performance degradation for being used at partial load. An estimation of the impact of this effect in energy performance predictions reduces the discrepancies to values around 5%. (C) 2010 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据