Thermoeconomic analysis and optimization of high efficiency solar heating and cooling systems for different Italian school buildings and climates

期刊

ENERGY AND BUILDINGS
卷 42, 期 7, 页码 992-1003

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2010.01.011

关键词

Solar energy; Evacuated collectors; Absorption chiller; Dynamic simulation; Renewable energy

向作者/读者索取更多资源

The paper investigates the energetic and economic feasibility of a solar-assisted heating and cooling system (SHC) for different types of school buildings and Italian climates. The SHC system under investigation is based on the coupling of evacuated solar collectors with a single-stage LiBr-H2O absorption chiller: auxiliary energy for both heating and cooling is supplied by an electric-driven reversible heat pump. The SHC system was coupled with different types of school buildings located in three different Italian climatic zones. The analysis is carried out by means of a zero-dimensional transient simulation model, developed using the TRNSYS software: the analysis of the dynamic behaviour of the building was also included. An economic model is proposed, in order to assess the operating and capital costs of the systems under analysis. Furthermore, a parametric analysis and a subsequent mixed heuristic-deterministic optimization algorithm was implemented, in order to determine the set of the synthesis/design variables that maximize system profitability. The results are encouraging, as for the potential of energy saving. On the contrary, the SHC economic profitability can be achieved only in case of public funding policies (e.g. feed-in tariffs), as always happens for the great majority of renewable energy systems. (C) 2010 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据