Performance evaluation of an off-grid photovoltaic system in Saudi Arabia

期刊

ENERGY
卷 46, 期 1, 页码 451-458

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.energy.2012.08.004

关键词

PV system; Solar radiation; DC performance ratio; PV panel surface temperature; PV efficiency

资金

  1. Center of Research Excellence in Renewable Energy at KFUPM [CoRE-RE-07]

向作者/读者索取更多资源

The paper presents the performance evaluation analysis of a 5.28 kW installed capacity isolated grid photovoltaic power plant installed at King Fahd University of Petroleum and Minerals, Dhahran Saudi Arabia in June 2010. The plant was equipped with temperature, solar radiation intensity, and PV (Photovoltaic) panel power output recording sensors for performance evaluation of the plant. The analysis presented the effect of PV surface temperature and dust collected on the panels on the power output of individual arrays and total power from complete plant. Furthermore, the PV panel performance was studied by DC (Direct current) performance ratio variation with PV panel backside surface temperature. Hourly mean energy yield was found to be decreasing with increasing PV panel surface temperature during the months of July & August 2010. The daily energy yield showed a decreasing trend with days of the month which could be accounted for dust accumulation on the PV panel surface. The DC performance ratio also showed a decreasing trend with increasing PV panel surface temperature. (C) 2012 Elsevier Ltd. All rights reserved.