4.7 Article

An experimental comparison of two heat exchangers used in wastewater source heat pump: A novel dry-expansion shell-and-tube evaporator versus a conventional immersed evaporator

期刊

ENERGY
卷 47, 期 1, 页码 600-608

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.energy.2012.09.043

关键词

Wastewater source heat pump; Immersed evaporator; Dry-expansion; Shell-and-tube evaporator; Water heating

资金

  1. National Key Technology R&D Program in the 11th Five Year Plan of China [2006BAJ01A06]
  2. University of Illinois at Urbana-Champaign

向作者/读者索取更多资源

A novel dry-expansion shell-and-tube evaporator (DESTE) integrated with function of defouling was developed as a component of wastewater source heat pump (WWSHP). To compare the performance of the DESTE-VVWSHP with the conventional immersed evaporator (IE) based wastewater source heat pump (IE-WWSHP), an experimental platform was built by installing a DESTE and an IE unit in parallel in a same WWSHP system. The performance tests were conducted with the wastewater collected from downstream of a commercial sauna center in Shenzhen, China. Several operating parameters were investigated, including water heating capacity, coefficient of performance (COP), hot water temperature settings, wastewater discharge rate/pattern, and hot water discharge mode (continuous or intermittent). Results showed that the DESTE-VVWSHP delivered comparable heat transfer performance to the IE-WWSHP, and thus, could serve as a replacement for the latter design. Specifically, the water temperature in the water storage tank was more uniformly distributed in the DESTE-WWSHP than the IE-WWSHP; the DESTE-WWSHP exhibited higher water heating capacity than the IE-WWSHP in the continuous hot water discharge mode. The DESTE has a heat transfer coefficient 3.1 times higher than that of the IE unit on the wastewater side. At the same heating capacity, the DESTE was far more compact with its compactness 7 times higher and its volume 91.71% smaller than the IE unit, leading to considerable savings in room space and materials. Additional benefits offered by this DESTE-WWSHP included reduced labor and power costs for cleaning heat exchanger, and decreased odor nuisance. (C) 2012 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据