4.6 Article

Modeling of a PV system with grid code compatibility

期刊

ELECTRIC POWER SYSTEMS RESEARCH
卷 116, 期 -, 页码 301-310

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.epsr.2014.06.021

关键词

PV; Grid codes; LVRT; Dynamic model; PLL; LCL filter

向作者/读者索取更多资源

Increasing penetration of Renewable Energy Sources (RES) to the power systems leads to the continuous evolution of grid interconnection requirements, which now include Low Voltage Ride Through (LVRT) practically for all types of generating units connected to the MV or HV networks, including photovoltaics (PV). It is essential that the Distributed Generation (DG) models used in power system studies properly represent the enhanced response characteristics of the stations. In this paper, a model is presented for a PV system with grid-code compatibility, which is suitable for power system dynamic and transient analysis studies. For this purpose, an overall control strategy is introduced to achieve LVRT capability, while elements essential for the correct representation of the dynamic performance of the system, such as the Phase Locked Loop (PLL) and the output LCL filters, are properly accounted for. Time domain simulations are provided for balanced and unbalanced voltage dips, in order to demonstrate the performance of the PV system and evaluate the accuracy of the proposed simplified model. The response of the detailed switching model is also included in the simulation results. (c) 2014 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据