4.6 Article

AGC of a multi-area thermal system under deregulated environment using a non-integer controller

期刊

ELECTRIC POWER SYSTEMS RESEARCH
卷 95, 期 -, 页码 175-183

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.epsr.2012.09.008

关键词

Automatic generation control; Bacterial foraging; Classical controller; Fractional order controller; DISCO Participation Matrix

向作者/读者索取更多资源

This paper presents automatic generation control (AGC) of multi-area thermal systems under deregulated environment considering reheat turbines and appropriate generation rate constraints (GRC). The performance of a fractional-order Proportional-Integral-Derivative (FOPID) controller is evaluated for the first time in AGC of the proposed systems. Performances of several integer order (10) controllers have been evaluated and are compared with FOPID controller. Investigation reveals that FOND controller provides better dynamic performance than the 10 controllers in both equal and unequal area system. Bacterial foraging (BF) technique is used for simultaneous optimization of the gains and other parameters such as order of integrator (lambda) and differentiator (mu) in case of FOPID controller and speed regulation parameter (R) and such optimization results higher value of R which is welcome for simple and cheaper realization of governor. Further, Sensitivity analysis is carried out for the first time in the system considered to investigate the robustness of the optimum gains, lambda and mu of FOPID controllers and R parameters obtained at nominal condition. Analysis expose that parameters obtained at nominal conditions need not be reset to wide changes in system condition, parameters, size and position of step load perturbation (SLP). Investigations on higher order of contract violation reveal that FOPID controller performed better than other 10 controller. (c) 2012 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据