期刊
IEEE TRANSACTIONS ON POWER DELIVERY
卷 17, 期 1, 页码 233-241出版社
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/61.974212
关键词
classifier; hidden Markov model (HMM); power disturbances; wavelet packet
This paper presents a novel classification method for power distribution line disturbances using a rule-based method and a wavelet packet-based hidden Markov model (HMM). The rule-based method is utilized for the classification of time-characterized-feature disturbances, and the wavelet packet-based HMM is utilized for the frequency-characterized-feature power disturbances. This proposed method classifies six types of actual recorded power distribution disturbances, i.e., sag, interruption, fast capacitor switching, capacitor switching, normal variation, and impulse disturbance, and obtains 98.7% correct classification rate for 670 actual disturbance events tested.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐