4.6 Article

Experimental facility for investigation of lightning performance of distribution lines

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 18, 期 1, 页码 253-257

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2002.803844

关键词

direct stroke; distribution line; EMTP; natural lightning; surge arrester

向作者/读者索取更多资源

In order to clarify the lightning performance of a distribution line, test distribution lines and a test tower were constructed at the Mikuni Testing Center of Hokuriku Electric Power Company in 1999. Using these facilities, we observed transient voltages and current distributions due to direct strokes of natural lightning. Based on this data, we have clarified the following points: 1) Calculated voltages and currents using the EMTP agree with the experimental results fairly well. 2) For lightning currents of long durations, however, the reduction of voltages across arresters by energy absorption should be taken into consideration.