4.6 Article Proceedings Paper

Thermal comfort standards for air conditioned buildings in hot and humid Thailand considering additional factors of acclimatization and education level

期刊

SOLAR ENERGY
卷 78, 期 4, 页码 504-517

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.solener.2004.07.006

关键词

comfort survey; acclimatization; climatic regions; education

向作者/读者索取更多资源

This paper presents the result of a large thermal comfort survey conducted using 1520 Thai volunteers from different climatic regions of Thailand. The survey was conducted using different types of air-conditioned buildings from the private and public sectors. Apart from common thermal comfort factors such as air dry bulb temperature, relative humidity and air velocity, two non -quantifiable factors were considered. These are the acclimatization to the use of air conditioner at home and the education level, i.e., post graduate, graduate and scholar. A general database for thermal comfort studies in Thailand was created, and different thermal comfort standards were developed for the three climatic regions of Thailand. Twenty six degree Celsius and 50-60% relative humidity could be used as a comfortable environment condition for the whole country. The data was then used to generalize an earlier concept we developed for setting thermal comfort standard using data from non air-conditioned buildings. (c) 2004 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据