4.5 Article Proceedings Paper

How to treat raw sewage with constructed wetlands: an overview of the French systems

期刊

WATER SCIENCE AND TECHNOLOGY
卷 51, 期 9, 页码 11-21

出版社

I W A PUBLISHING
DOI: 10.2166/wst.2005.0277

关键词

vertical flow constructed wetlands; raw sewage; data collection; design; performance

向作者/读者索取更多资源

The development of vertical flow constructed wetlands treating raw wastewater in France has T Z proved to be very successful over the last 20 years. In view of this a survey was carried out on more than 80 plants in order to study their performance and correct the design if necessary. This study shows that such V systems perform well in terms of respecting the goals of both low level outlet COD and SS and nitrification. Pollutant removal performance in relation to the loads handled and the specific characteristics of the plants were investigated. Nitrification is shown to be the most sensitive process in such systems and performance ) in relation to sizing is discussed. Such systems, if well designed, can achieve an outlet level of 60 mg L-1 in COD, 15 mg L-1 in SS and 8 mg L-1 in TKN with an area of 2-2.5m(2). PE-1. The sludge deposit on the first stage must be removed after about 10-15 years.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据