期刊
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID
卷 30, 期 1, 页码 155-165出版社
ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2006.06.005
关键词
refrigerant; R-410A; experiment; heat transfer; boiling; horizontal tube; microchannel
Convective boiling heat transfer experiments were performed in horizontal minichannels with binary mixture refrigerant, R-410A. The test section is made of stainless steel tubes with inner diameters of 1.5 mm and 3.0 mm and with lengths of 1500 mm and 3000 mm, respectively, and is uniformly heated by applying electric current directly to the tubes. Local heat transfer coefficients were obtained for a heat flux range of 10-30 kW m(-2), a mass flux range of 300-600 kg m(-2) s(-1), and quality ranges of up to 1.0. The experimental results were mapped on Wang et al.'s (C.C. Wang, C.S. Chiang, D.C. Lu, Visual observation of two-phase flow pattern of R-22, R-134a, and R-407C in a 6.5-mm smooth tube, Experimental, Thermal and Fluid Science 15 (1997) 395-405) and Wojtan et al.'s (L. Wojtan, T. Ursenbacher, J.R. Thorne, Investigation of flow boiling in horizontal tubes: part I - a new diabatic two-phase flow pattern map, International Journal of Heat and Mass Transfer 48 (2005) 2955-2969) flow pattern maps to observe the flow regimes. Laminar flow appears in flow with minichannels. A new boiling heat transfer coefficient correlation based on the superposition model for R-410A was developed with 11.20% mean deviation; it showed a good agreement between the measured data and the calculated heat transfer coefficients. (c) 2006 Elsevier Ltd and IIR. All rights reserved.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐