4.7 Article

Experimental analysis of the transport of airborne contaminants between adjacent rooms at different pressure due to the door opening

期刊

BUILDING AND ENVIRONMENT
卷 81, 期 -, 页码 81-91

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2014.05.031

关键词

Infective-aseptic room contamination; Differential pressurization; Door operation effect; Dirty air transfer

向作者/读者索取更多资源

Today it is common practice to try and obtain airborne contamination control through pressurization-depressurization areas. Moreover, there is some qualitative evidence that turbulence induced by the operation of a door between different pressure areas, could overcome the differential pressurization effect, and cause a pouring effect between zones, and consequently a contamination. The paper investigates the described matter through an experimental setup, with a scale physical model. Obtained results confirm that door operation is able to produce a dirty air transfer in the clean room, and that transfer entity is almost independent from differential pressure and flow rate imbalance, at least for the experimentally tested values, while it appears strongly related to air volume displaced in the door opening operation, and has the same order of magnitude of it. (C) 2014 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据