4.7 Article

Comfort under personally controlled air movement in warm and humid environments

期刊

BUILDING AND ENVIRONMENT
卷 65, 期 -, 页码 109-117

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2013.03.022

关键词

Thermal comfort; Perceived air quality; Warm-humid; Air movement; Personal control; Low energy

资金

  1. National Natural Science Foundation of China [50978102, 50838003]
  2. California EPA Air Resource Board [10308]
  3. Center for the Built Environment
  4. UC Berkeley
  5. Program for New Century Excellent Talents in University
  6. National Key Technology R&D Program of China [2011BAJ01B01]

向作者/读者索取更多资源

This study examined the effects of personally controlled air movement on human thermal comfort and perceived air quality (PAQ) in warm-humid environments. At temperatures 26, 28, and 30 degrees C, and relative humidity (RH) 60% and 80%, sixteen human subjects were exposed to personally controlled air movement provided by floor fans in an environmental chamber. The subjects reported their thermal sensation, thermal comfort, and PAQ during the tests. Two breaks periods with elevated metabolic levels were used to simulate normal office activities. Results show that with personally controlled air movement, thermal comfort could be maintained up to 30 degrees C and 60% RH, and acceptable PAQ could be maintained up to 30 degrees C 80% RH, without discomfort from humidity, air movement or eye-dryness. Thermal comfort and PAQ were resumed within 5 min after the breaks. The 80% acceptable limit implicit in comfort standards could be extended to 30 degrees C and 60% RH. The average energy consumed by the fans for maintaining comfort was lower than 10 W per person, making air movement a very energy-efficient way to deliver comfort in warm-humid environments. (c) 2013 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据