4.7 Article

The airborne transmission of infection between flats in high-rise residential buildings: Particle simulation

期刊

BUILDING AND ENVIRONMENT
卷 44, 期 2, 页码 402-410

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2008.03.016

关键词

Particles; Lagrangian method; Eulerian method; Transport; Deposition

资金

  1. Research Grant Committee of Hong Kong SAR [PolyU 5125/04E]
  2. Infectious Disease Control [03040642]

向作者/读者索取更多资源

Several case clusters occurred in high-rise residential buildings in Hong Kong in the 2003 SARS (the severe acute respiratory syndrome) epidemic, which motivated a series of engineering investigations into the possible airborne transport routes. It is suspected that, driven by buoyancy force, the polluted air that exits the window of the lower floor may re-enter the immediate upper floor through the window on the same side. This cascade effect has been quantified and reported in a previous paper, and it is found that, by tracer gas concentration analysis, the room in the adjacent upstairs may contain up to 7% of the air directly from the downstairs room. In this study, after validation against the experimental data from literatures, Eulerian and Lagrangian approaches are both adopted to numerically investigate the dispersion of expiratory aerosols between two vertically adjacent flats. It is found that the particle concentration in the upper floor is two to three orders of magnitude lower than in the source floor. 1.0 mu m particles disperse like gaseous pollutants. For coarse particles larger than 20.0 mu m, strong deposition on solid surfaces and gravitational settling effect greatly limit their upward transport. (C) 2008 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据