期刊
BUILDING AND ENVIRONMENT
卷 44, 期 2, 页码 368-376出版社
PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2008.03.011
关键词
LCC; Life cycle cost; Indoor climate systems; Productivity; Energy; Health
The life cycle cost (LCC) of the heating, cooling and ventilation system was simulated for a typical cell office building, multi-family dwelling and detached house. Different ventilations systems were simulated resulting in different heating and cooling system designs. A health-related cost dependent on the airflow rate which was based on recent studies was added to the LCC for the dwellings as well as a productivity cost for the office building. An optimal airflow rate can be found depending on the assumed size of the health or productivity-related cost. The results for the office building indicate that a much higher outdoor supply airflow rate at presence, as well as a cooling system, is appropriate from a LCC perspective even if the influence on the human being still should be taken with precaution. With that higher airflow rate, the results show that there is a clear benefit with variable airflow rate ventilation systems. For dwellings, there is also a clear benefit from higher airflow rates even if the optimal airflow rate in the presented examples was not much higher than common requirements. Furthermore, it is not well known or defined how to valuate that possible influence. Despite this, this study is the demonstration of a method which can be used to optimize airflow rates in buildings if the influence and costs on human health related to the airflow rate is known. (C) 2008 Elsevier Ltd. All rights reserved.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐