Designing coaxial ground heat exchangers with a thermally enhanced outer pipe

期刊

GEOTHERMAL ENERGY
卷 3, 期 -, 页码 -

出版社

SPRINGER
DOI: 10.1186/s40517-015-0027-3

关键词

Geothermal; Heat pump; Ground heat exchanger; Borehole; Coaxial; Concentric; Pipe; Thermally enhanced

向作者/读者索取更多资源

Background: Ground heat exchangers installed in boreholes are an expensive component of a ground-coupled heat pump system, where minimizing the borehole length with appropriate materials and configuration can reduce the overall cost of the system. Methods: Design calculations performed analytically indicate that the coaxial pipe configuration can be more advantageous than the single U-pipe configuration to reduce the total borehole length of a system. Results: A decrease of the borehole thermal resistance and an increase of the thermal mass of water contained in the coaxial exchanger helped to reduce borehole length by up to 23% for a synthetic building load profile dominated by cooling. The decrease of the borehole thermal resistance was achieved with an outer pipe made of thermally enhanced high-density polyethylene, where the thermal conductivity is 0.7 W m(-1) K-1. Conclusions: The coaxial configuration requires further investigations of the technical barriers related to the installation of ground heat exchangers in the field.