4.6 Article

Investigation of the use of inverter control strategy instead of synchronous condensers at inverter terminal of an HVDC system

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 15, 期 2, 页码 704-709

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/61.853008

关键词

HVDC transmission control; power system dynamic stability

向作者/读者索取更多资源

This paper presents a comparison of performance of traditionally used Synchronous Condensers (SC's) at inverter side HVDC terminal and a novel inverter control method. The novel controller has earlier demonstrated good responses with very weak inverter AC systems and widely changing AC system parameters. The aim of this research is to study if it is possible to offer adequate replacement for SC at weak HVDC -HVAC interconnection point. The simulation results on an actual HVDC system show excellent small signal responses, but the main obstacle for the application of the new control method could be increased probability of commutation failure. Subsequent tests show that in order to keep the same commutation failure probability, half of the SC must be maintained in normal operation. Further SC can also be disconnected, when the new control method is employed, however the nominal operating angle has to be somewhat increased. The cost benefit study is performed to analyze the financial benefits of the proposed project. It is concluded that, although the benefits are evident for the new HVDC links, the proposed replacement of SC may not be justifiable for the existing links.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据