4.6 Article

Decreasing the commutation failure frequency in HVDC transmission systems

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 15, 期 3, 页码 1022-1026

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/61.871369

关键词

commutation failures; digital control; HVDC; transmission

向作者/读者索取更多资源

In this paper we show how a fairly targe proportion of those commutation failures that are due to single-phased short circuits to earth can he avoided. In a control circuit based on a digital signal processor (DSP) it is possible, with instantaneous results, to switch from a normal control strategy with equidistant firing pulses to a strategy that takes into consideration the potentially dangerous voltage changes on the supply lines, IF the supply voltages are monitored continuously, it is possible to calculate the necessity of advancing the bring pulses to avoid commutation failures, In the paper such a calculation technique is described. The monitoring times may be approximately 50 mu sec apart corresponding to a distance of 0.016 radians or about 1 degrees.