4.6 Article

Correlation of two-phase friction for refrigerants in small-diameter tubes

期刊

EXPERIMENTAL THERMAL AND FLUID SCIENCE
卷 25, 期 3-4, 页码 131-139

出版社

ELSEVIER SCIENCE INC
DOI: 10.1016/S0894-1777(01)00066-8

关键词

two-phase; pressure drop; correlation; refrigerant; micro-channel

向作者/读者索取更多资源

Single-phase and adiabatic two-phase flow pressure drop were measured for R-134A, R-22 and R-404A flowing in a multi-port extruded aluminum tube with hydraulic diameter of 2.13 mm, and in two copper tubes having inside diameters of 6.25 and 3.25 mm, respectively. The single-phase friction factor was predicted within +/-10% using the Blasius friction correlation. The Friedel correlation did not predict the two-phase data accurately, especially for high reduced pressure. Using the data taken in the present and in a previous study, a new correlation for two-phase friction pressure drop in small diameter tubes was developed by modifying the Friedel correlation. The new correlation predicts 119 data points with a mean deviation of 11.5%. (C) 2001 Elsevier Science Inc. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据