4.7 Article

The effect of the number of tube rows on heat, mass and momentum transfer in flat-plate finned tube heat exchangers

期刊

ENERGY
卷 26, 期 11, 页码 963-972

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/S0360-5442(01)00048-2

关键词

-

向作者/读者索取更多资源

The effect of the number of tube rows on heat, mass and momentum transfer is experimentally investigated for flat-plate, finned-tube heat exchangers which consist of aluminum. fins and copper tubes. Four flat-plate finned-tube heat exchangers are identical except for changes in the number of tube rows (1 to 4). Heat-transfer coefficients for wet and dry surface conditions are obtained for both heating and cooling of moist air flowing over finned tubes. The air velocity was varied from 0.9 to 4 m/s. Heat transfer, Colburn and friction factors are determinated for different tube rows numbers while the Reynolds number were being warried. It is found that the values of Colburn and friction factors for wet surfaces are higher than for dry surfaces and for both conditions the Colburn and friction factors decrease with an increase in the tube row numbers. (C) 2001 Elsevier Science Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据