4.6 Article

A detection algorithm for islanding-prevention of dispersed consumer-owned storage and generating units

期刊

IEEE TRANSACTIONS ON ENERGY CONVERSION
卷 16, 期 4, 页码 346-351

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/60.969474

关键词

dispersed generating units; islanding

向作者/读者索取更多资源

One of critical concerns in the operation of grid-connected dispersed generating units is the occurrence of islanding. It is known that the islanding may pose hazards to utility personnel and complicate the orderly reconnection of grid. Hence, in this paper, a new algorithm based on the monitoring of the change in partial derivativef/partial derivativeP(L) to detect the islanding is proposed. By the proposed method, a detection index can be evaluated that serves as a useful reference to activate the protective relays. This approach has been applied to investigate different scenarios, including the loss of grid and the parallel operation. Effects of load change and power-quality disturbances to the detection performance are also examined. From these test results, they help solidity the feasibility and effectiveness of the approach for the applications considered.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据