期刊
ATMOSPHERIC ENVIRONMENT
卷 43, 期 28, 页码 4311-4318出版社
PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.atmosenv.2009.06.002
关键词
Indoor; Fine particle; Mixing; Concentration heterogeneity; Flow field; Experimental studies
资金
- Natural Science Fund of China (NSFC) [10502044]
- Natural Science Foundation of Zhejiang Province (ZJNSF) [Z107332]
The mixing processes of the aerosol particles from an outdoor environment in a ventilated scale chamber were experimentally studied. The particles were classified into five groups by size: 0.3-0.5 mu m, 0.5-1.0 mu m, 1.0-3.0 mu m, 3.0-5.0 mu m and 5.0-10.0 mu m. The developing process for the concentration of each particle group was measured in different kinds of flow fields. The results show that the flow field configuration can effectively influence the dispersion time rate of the particles at certain positions. The increase in particle diameter can decrease the dispersion time rate. When the gas flow velocity is high, the particle dispersion time rate is independent of particle size; but when the gas flow velocity is low, particle size can significantly affect the particle dispersion time rate because the turbulent diffusion becomes important in the air and particle transport. The uniformity of the particle concentration for certain positions in steady state tends to be controlled by the inflow velocity, flow field configuration and the particle diameters. (C) 2009 Elsevier Ltd. All rights reserved
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐
暂无数据