3.9 Article Proceedings Paper

Smart pumpless loop for micro-channel electronic cooling using flat and enhanced surfaces

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TCAPT.2003.811478

关键词

boiling; critical heat flux; high heat flux; microchannel; passive cooling; phase change; pumpless loop; pressure drop

向作者/读者索取更多资源

Two-phase cooling of a square simulated electronic device surface of 21.3 mm side was successfully carried out without the need for a pump. This smart, passive cooling system incorporates a self-enhancing and self-sustaining mechanism, wherein the system inherently enhances its cooling capacity by increasing the velocity of the two-phase mixture along the boiling surface when an increase in heat flux is sensed. Other practical attributes of this pumpless loop are small liquid inventory requirements and absence of the incipient boiling temperature drop. It is shown small surface tension and contact angle render dielectric coolants such as FC-72 ideally suited for flow in narrow gaps. These unique properties are responsible for very small bubble size, precluding any appreciable blockage of the replenishment liquid flow even in narrow gaps. Critical heat flux (CHF) was found to generally increase with decreasing boiler gap. CHF for flat, micro-channel (with 0.2 mm rectangular fins) and mini-channel (with 1.98 mm rectangular fins) surfaces was 4.5, 5.9, and 5.7 times greater than for pool boiling from a flat surface for corresponding gaps. A pressure drop model was formulated to predict coolant mass flow rate, boiling surface inlet and exit velocities, and pressure drop components throughout the loop. The model predictions illustrate the pumpless loop's self-sustaining and self-enhancing attributes, and relate CHF trends to those of the two-phase mixture acceleration along the boiling surface.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

3.9
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据