4.7 Article

AHU sensor fault diagnosis using principal component analysis method

期刊

ENERGY AND BUILDINGS
卷 36, 期 2, 页码 147-160

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2003.10.002

关键词

fault diagnosis; sensor fault; principal component analysis; air handling unit

向作者/读者索取更多资源

The paper presents a strategy based on the principal component analysis (PCA) method, which is developed to detect and diagnose the sensor faults in typical air-handling units. Sensor faults are detected using the Q-statistic or squared prediction error (SPE). They are isolated using the SPE and Q-contribution plot supplemented by a few simple expert rules. Two PCA models are built based on the heat balance and pressure-flow balance of the air-handling process, aiming at reducing the effects of the system non-linearity and enhancing the robustness of the strategy in different control modes. The fault isolation ability of the method is improved using the multiple models. Simulation tests and site data from the building management system (BMS) of a building are used to verify the PCA-based strategy for automatic validation of AHU monitoring instrumentations and detecting/isolating AHU sensor faults under typical operating conditions. The robustness of the PCA-based strategy in detecting/diagnosing AHU sensor faults is verified. Effects of sensor faults and the strategy energy efficiency of an automated AHU are evaluated using simulation tests. (C) 2003 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据