4.7 Article

Control and energy simulation of variable refrigerant flow air conditioning system combined with outdoor air processing unit

期刊

APPLIED THERMAL ENGINEERING
卷 64, 期 1-2, 页码 385-395

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2013.12.076

关键词

Combined air conditioning system; Variable refrigerant flow; Outdoor air processing; Indoor air quality; Part load ratio

资金

  1. National Natural Science Foundation of China [51376125, 51376126]

向作者/读者索取更多资源

A variable refrigerant flow (VRF) unit and outdoor air (OA) processing unit combined air conditioning system is proposed as a solution for ventilation problems in VRF systems. System structure and control strategies are addressed. Simulation platform is established based on component and sub-system models developed. Control and energy performances analysis are then put forward under various conditions. It is found that the combined system could maintain all the zones at their specific set-points within small errors no matter set-points of the zones are the same or different. In addition, indoor air quality can be ensured. Energy efficiency characteristics of the combined system are greatly affected by the OA supply temperature of the OA processing unit, which opens up the opportunity of minimizing the energy consumption of the combined system through optimal control strategy. Results reveal that the best OA supply temperature can be obtained through optimizing part load ratio of the OA processing unit to a range in which the system operates with high efficiency. (C) 2014 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据