4.7 Article

The exergy and energy level analysis of a combined cooling, heating and power system driven by a small scale gas turbine at off design condition

期刊

APPLIED THERMAL ENGINEERING
卷 66, 期 1-2, 页码 590-602

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2014.02.066

关键词

CCHP system; Off-design performance; Energy level analysis; Exergy; Distributed energy system

资金

  1. National Key Fundamental Research Project [2010CB227306, 2013CB228302]
  2. National Natural Science Foundation of China [51176185]

向作者/读者索取更多资源

This paper presents the off design performance analysis of a combined cooling, heating, and power (CCHP) system consisting of a small-scale gas turbine, an exhaust-fired double-effect absorption chiller, and a heat exchanger. The energy and exergy analyses of the CCHP system are investigated under the rated and part-load conditions. Energy level analysis is implemented on the energy conversion processes to reveal the mechanisms of the deterioration of the CCHP performance under part-load conditions. The results show that the CCHP system is energy saving when the power output of the gas turbine exceeds 30% of the full load. It is also found that the CO2 emission of the CCHP system reduced by 66.7%-70.5%, compared with conventional separation system, when the power output of gas turbine increased from about 30% to 100%. Energy level results reveal that the combustor of the small-scale gas turbine mainly contributed to the deteriorated performance of the CCHP system. In addition, a case study is carried out to illustrate the advantage of using dynamic data in the performance assessment. The case results indicate that using off-design data leads to a more realistic evaluation of the CCHP system. (C) 2014 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据