4.7 Article

Numerical analysis and optimization of a solar hybrid one-rotor two-stage desiccant cooling and heating system

期刊

APPLIED THERMAL ENGINEERING
卷 73, 期 1, 页码 474-483

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2014.07.076

关键词

Desiccant cooling; Solar; Simulation; System optimization

向作者/读者索取更多资源

In this paper, a solar hybrid one-rotor two-stage desiccant cooling and heating system has been numerically analyzed. The system was made up of a one-rotor two-stage desiccant cooling unit, with design cooling capacity for 5 kW, and a solar collector array of 15 m(2). Performance model of the system was created in TRNSYS simulation studio. Firstly, base case performance models were programmed according to the configuration of the installed solar desiccant system and verified by the experimental data. Secondly, the year-round performance about the system was simulated. Finally, we optimized the parameters of the system, including the solar collector area, the ratio between fresh air and return air, and the heat exchanger efficiency. Numerical results agree with the experimental ones. The simulation results showed that about 60% of the humidity load can be totally handled by the one-rotor two-stage desiccant cooling unit, and about 40% of the heating load can be handled by solar energy. (C) 2014 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据