4.7 Article

Numerical study on the dispersion of airborne contaminants from an isolation room in the case of door opening

期刊

APPLIED THERMAL ENGINEERING
卷 29, 期 8-9, 页码 1544-1551

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2008.07.009

关键词

Isolation room; CFD; Airflow; Ventilation

资金

  1. National Science Council of Taiwan Republic of China

向作者/读者索取更多资源

A negative pressure isolation room is built to accommodate and cure patients with highly infectious diseases. An absolutely airtight space effectively prevents infectious diseases from leaking out of the isolation room. Opening the door leads to a breakdown in isolation conditions and causes the dispersion of infectious air out of the isolation room. Extensively employed to manage smoke in cases of fires at subway and highway tunnels, a concept of controlling airflow is applied to the study. This study proposes a design of ventilation system to control air flow rate for containing airborne contaminant and preventing its spread to the adjacent rooms when the door to the isolation room is opened and closed. This paper employs computational fluid dynamics (CFD) as a more effective approach to examine the concentration maps of airborne contaminants and the airflow patterns of room air and discuss the influence of temperature differences between two rooms on airborne dispersion. Results show that an air velocity above 0.2 m/s via a doorway effectively prevents the spread of airborne contaminants out of the isolation room in the state of door opening. (C) 2008 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据