4.5 Article

Containment testing of isolation rooms

期刊

JOURNAL OF HOSPITAL INFECTION
卷 57, 期 3, 页码 228-232

出版社

W B SAUNDERS CO LTD
DOI: 10.1016/j.jhin.2004.01.032

关键词

tracer; airborne infection; performance testing

向作者/读者索取更多资源

Results from the tracer containment testing of four 'state-of-the-art' airborne infection isolation rooms, in a new hospital, are presented. A testing technician exited an isolation room several minutes after a small quantity of tracer gas was injected over the patient bed in that room. Easily measurable tracer gas concentrations were then found in the anterooms outside the patient rooms and corridor outside the isolation room suites. Containment factors for the isolation rooms and dilution factors in the anterooms and corridor were calculated, based on the measured tracer concentrations. These results indicate the desirability of evidence-based design standards and guidelines for assessing performance of airborne infection isolation rooms. The study also demonstrates that the tracer testing procedure yields comparable results for equivalent isolation room suites, suggesting good reproducibility of the testing method. (C) 2004 The Hospital Infection Society. Published by Elsevier Ltd. All rights reserved.