Local heat transfer and pressure drop for finned-tube heat exchangers using oval tubes and vortex generators

期刊

出版社

ASME-AMER SOC MECHANICAL ENG
DOI: 10.1115/1.1795239

关键词

-

向作者/读者索取更多资源

This paper presents the results of an experimental study of forced convection heat transfer in a narrow rectangular duct fitted with an elliptical tube and one or two delta-winglet pairs. The duct was designed to simulate a single passage in a fin-tube heat exchanger Heat transfer measurements were obtained using a transient technique in which a heated airflow is suddenly introduced to the test section. High-resolution local fin-surface temperature distributions were obtained at several times after initiation of the transient using an imaging infrared camera. Corresponding local fin-surface heat transfer coefficients were then calculated from a locally applied one-dimensional semi-infinite inverse heat conduction model. Heat transfer results were obtained over a Reynolds number range based on duct height of 670-6300. Pressure-drop measurements have also been obtained for similar elliptical-tube and winglet geometries, using a separate single-channel, multiple-tube-row pressure-drop apparatus. The pressure-drop apparatus includes four tube rows in a staggered array. Comparisons of heat transfer and pressure-drop results for the elliptical tube versus a circular tube with and without winglets are provided. Mean heat transfer results indicated that the addition of the single winglet pair to the oval-tube geometry yielded significant heat transfer enhancement, averaging 38% higher than the oval-tube, no-winglet case. The corresponding increase in friction factor associated with the addition of the single winglet pair to the oval-tube geometry was very modest, less than 10% at Re-Dh = 500 and less than 5% at Re-Dh = 5000.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

3.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据