期刊
IEEE TRANSACTIONS ON POWER DELIVERY
卷 19, 期 4, 页码 1547-1552出版社
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2003.822544
关键词
asynchronous sampling; discrete Fourier transform (DFT); frequency measurement; phase measurement
Comprehensive analysis of discrete Fourier transform (DFT) error is given in this paper, including why it is accurate when used in the case of synchronous sampling and how error rises when sampling frequency does not synchronized to signal frequency. Simple but precise expressions of phase angle error and amplitude error are given. Practical formulas to calculate the true phase angle and amplitude are presented. The formulas are very simple and precise. Based on the formula to calculate true phase angle, a new frequency tracking method is developed. The proposed method can be calculated recursively. And, with notable accuracy improvement, the calculation burden is little more than the traditional DFT method. Also, an adaptive method to suppress the effect of harmonics is presented, which adds very little calculation burden with satisfying performance. The most distinguished feature of the proposed method is that it is not only precise, but also simple. Some examples are given to demonstrate the feasibility, precision, simpleness and robustness of the proposed method.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐
暂无数据