4.7 Article

Fault-tolerant control and data recovery in HVAC monitoring system

期刊

ENERGY AND BUILDINGS
卷 37, 期 2, 页码 175-180

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2004.06.023

关键词

faulty data; missed data; PCA; data recovery; fault-tolerant control; HVAC monitoring system

向作者/读者索取更多资源

It is necessary that a reliable and optimal control system has the ability of fault tolerance, which recovers the faulty and/or missed data in time. Principal component analysis (PCA) is presented to model HVAC monitored systems by using the measured data under normal operation condition (NOC). PCA splits the measurement space into two subspaces, one principal component subspace (PCS) and the other residual subspace (RS). When the faulty or missed data is observed, it will be projected into PCS and RS. It is then recovered by sliding the faulty or missed data to PCS via iteration. Examples of HVAC monitoring system have demonstrated that the approach has good performance to recover faulty or missed data and thus can be embedded into the system to achieve fault-tolerant control. (C) 2004 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据