Two-phase pressure drop was measured across a micro-channel heat sink that served as an evaporator in a refrigeration cycle. The micro-channels were formed by machining 231 mum wide x 713 mum deep grooves into the surface of a copper block. Experiments were performed with refrigerant R I 34a that spanned the following conditions: inlet pressure of Pi,, = 1.44-6.60 bar, mass velocity of G = 127-654 kg/m(2)s, inlet quality Of X,,in = 0.001-0.25, outlet quality of x(e,out) = 0.49-superheat, and heat flux of q() = 31.6-93.8W/cm(2). Predictions of the homogeneous equilibrium flow model and prior separated flow models and correlations yielded relatively poor predictions of pressure drop. A new correlation scheme is suggested that incorporates the effect of liquid viscosity and surface tension in the separated flow model's two-phase pressure drop multiplier. This scheme shows excellent agreement with the R I 34a data as well as previous micro-channel water data. An important practical finding from this study is that the throttling valve in a refrigeration cycle offers significant stiffening to the system, suppressing the large pressure oscillations common to micro-channel heat sinks. (C) 2004 Elsevier Ltd. All rights reserved.